Size: А А А Interval: AB AB AB Colors: А А А А Images: Включить графику Выключить графику
Regular versionRegular version

Oxygen generator MIL'S

PRO2XY® VAC 0,5 / 5 / 10 бар

  • Oxygen purity > 95%
  • Oil-free compression technology
  • Energy cost saving > 50% / PSA
  • Environment-friendly, compact design

  1. Oil-free vacuum pump
  2. Oil-free low pressure compressor
  3. VPSA oxygen generators 0,5 bar
  4. Buffer tank at 0,5 bar
  5. Oxygen compressor 5 bar
  6. Storage tank 5 bar
  7. Hospital network 5 bar
  8. 12 bar – oxygen booster
  9. 12 bar - storage tank
  10. Hospital network 12 bar

OXYGEN GENERATOR VPS

Energy comparison

VPSA technology 27 m3/h    39,3%

Energy saving 60.7%

PSA technology 27 m3/h    100%

HIGHT PRESSURE OPTION

11. 200 bar – oxygen booster
12. Rack of HP cylinders
13. HP filling skid for mobile cylinders

Technical characteristics

PRO2XY®  VAC  0,8

PRO2XY®  VAC 1,6

PRO2XY®  VAC 3,6

Oxygen purity

80%

90%

93%

95%

80%

90%

93%

95%

80%

90%

93%

95%

Flow rate in Nl/min

24

19,1

16,1

13,3

48

38,1

32,3

26,7

108

85,8

72,6

60

Flow rate in Nm3/h

1,44

1,14

0,97

0,8

2,88

2,29

1,94

1,6

6,48

5,15

4,36

3,6

Real consummated energy at 0,5 bar

0,81 kW

1,43 kW

3,44 kW

Required installed power at 0,5 bar

1,33 kW

1,71 kW

4,1 kW

Real consummated energy at 5 bar

1,4 kW

2,11 kW

4,32 kW

Required installed power at 5 bar

2,43 kW

2,81 kW

5,2 kW

Real consummated energy at 12 bar

1,45 kW

2,21 kW

4,56 kW

Required installed power at 12 bar

2,43 kW

2,81 kW

5,2 kW

Generator 1. L*W*H (mm)

1540 * 750 * 1950

2020 * 750 * 1950

Weight

450kg

530 kg

750 kg

Buffer tank 0,5 bar – Volume

200 l

2. Storage tank 1 бар  L*W*H (mm)

600* 600 * 1700

Weight – Volume

80 kg – 230 l

Noise level at 5 bar

72 dB (А)

73 dB (А)

74 dB (А)

PRO2XY®  VAC  18

PRO2XY®  VAC  27

Oxygen purity

80%

90%

93%

95%

80%

90%

93%

95%

Flow rate at Nm3/h

35,5

27,6

22,8

18,5

51,8

40,2

33,2

27

Real consummated energy at 0,5 bar

9 kW

13,2 kW

Required installed power at 0,5 bar

17 kW

19 kW

Real consummated energy at 5 bar

12,2

11,8 kW

11,6

11,3

17,3

16,6

16,3 kW

15,9

Required installed power at 5 bar

21 kW

27

23 kW

Real consummated energy at 12 bar

14

13.2 kW

12,7

12,3

20,1

18,7

17,9 kW

17,3

Required installed power at 12 bar

23,2 kW

30,7

26,7

25,2 kW

Vacuum pump 1 L*W*H (mm) - Weight

1150*970*1290 – 325 kg

1150*970*1290 – 425 kg

Low pressure compressor 2 L*W*H (mm) - Weight

960*780*1200 – 295 kg

960*780*1200 – 305 kg

Generator 3 L*W*H (mm) - Weight

1177*1634*1940 – 1000 kg

1296*1734*2186 – 1360 kg

Compressor 4 5 6 7 8 L*W*H (mm) - Weight

1420*2210*2180 – 850 kg

1750*2380*2350

1420*2210*2180  850 kg

985 kg

890 kg

Buffer tank 0,5 бар 4 - Volume

1000 l

1500 l

1000 l

Buffer tank 5 bar 6 - Volume

1000 l

1500 l

1000 l

Storage tank 12 bar 9 L*W*H (мм) – Weight - Volume

1140*1055*1940 – 255 kg – 1000l

1240*1155*2350 – 325kg – 1500l

1140*1055*1940 – 255kg – 1000l

Noise level at 5 bar

73,4 dB (А)

74,2 dB (А)